top of page

All final circuits must have a CPC

All CPCs must be connected to the star point of the local transformer with a low resistance connection. 

 

Max Ze

Each system has a maximum impedance Ze Allowed under ESQCR 2002 

TNS 0.8Ω

TNC-S 0.35Ω

TT 21Ω at the transformer 200Ω at ccu

 

When the supply cable is SWA, it is normally 2-core (L&N) and the steel armouring is used as the earth conductor. 

 

In a TNCs system the earth and neutral are seperate in the final circuits as usual. But they are combined in the supply from the transformer. 

 

 

Maximum disconnection times for 230v AC supplies using TN earthing systems

Final circuits up to and including 32A 0.4s

All other circuits (incl. distribution circuits) 5s

 

Disconnection times

The more current that flows the faster the disconnection time. 

To achieve fast disconnection times we need lots of fault current. 

 

We must design our circuits so that if a fault occurs, then as much fault current will flow as possible. 

To ensure that fault current are high, ohms law tell us we must have a low impedance - for the whole of the fault loop Zs

 

short circuit

A live conductor is any conductor that carried current in normal service (no faults) 

For single-phase circuits a short circuit could be contact between line and neutral L-N

For three phase circuits a short circuit could be contact between line and neutral L-N or between phases L-L (400v) 

 

Short circuits can have very little resistance between conductors so the fault current can be as high as 1,00s or 10,000 of amps, sometimes more.

 

 

Extra hazards

What are the extra hazards and risks with electricity on-site?

mechanical damage from: construction activities

                                               Vehicles

                                               Plant

                                               Abrasive materials

 

Weather - IP codes. 

Chemicals - corrosive - acid/alkali. 

Earthed metal - higher fault current

 

 

Voltage bands. 

CTE (Centre tapped earth) Transformer 

Step down tranformer. 

230v:110v

 

 

 

 

Protective multiple earthing (pme)

What is it and when is it required? 

 

PEN (protective earth and neutral) 

Hazrds of overhead conductors

Contact with line conductor. 

What happens if there is a break in the pen? 

 

No current flows so there is no volt drop

any circuit that is switched on at thr time connects the neutral to the line conductor through the load. so the neutral becomes live. 

All  the neutrals are connected in the ccu so all the neutrals become live .

Also because it is TNC-S the neutral tail is connected to the earthing system in the cutout .

Anything that is earthed or bonded becomes life. I.e all exposed and extraneous conductive parts have 230v 

also because no current can flow, all mcb's and rcb's stop working. 

 

Solution: PME (protective multiple earthing) 

Extra earth electrodes are connected to the pen conductor at regular intervals along the supply

 

This forms a mini TT system around the break in the pen conductor, connecting neutral and earth. 

 

Keypoints:

PME consists of earth electrodes connected to the PEN conductor at regular intervals along the supply. 

It provides an alternative route for neutral and fault (earth) currents if the PEN conductor is damaged

PME is required for two-wire overhead supplies to TNC-S systems

Before converting TT to TNC-S, it must be confirmed by the supply company that the supply is PME. 
 

 

 

Overcurrent devices 1

Device characterstics

overcurrent has 3

-Rating

The lowest current that can make the device opperate. 

MCB's usually avaliable as 6A, 10A, 20A, 32A and 40A or 45A.

 

 

-Breaking capacity

The highest current that the device can safely interrupt

Very large currents passing through fuses or MCB's can create extremely dangerous situations

Fuses:

Overcurrents normally cause the fuse element to melt

Very large currents cause the fuse element to vaporise with such force it can rupture the fuse casing resulting in explosion and fire.

This can damage or obliterate nearby equipment.

MCB's:

As well as thr possibility of components exploding, MCB's can present another hazard under certain circumstances. 

Contact breakers are two solid conductors held together inside each MCB. 

When the MCB operates, these contact breakers are allowed to spring apart. 


So every overcurrent device can cause serious problems if too much current passes through it. But how much is too much? 

Any current above the breaking capacity of the device means that the device may not safely interrupt the current, (ie not safely disconnect the circuit)

 

 

-Type (B,C or D) 

Some appliances and fixed loads draw more current when they are switched on, then settle to their full load current. 

They are known as: INRUSH CURRENTS

Inrush currents are usually caused by inductors. 

 

Type B

Instantaneous trip above 5x rating, All circuits that have only resistive loads

Type C

Instantaneous trip above 10x rating

Examples: Moderate inductive loads:

Small or meduim motors

transformers

flourescent lighting circuits. 

Tybe D 

Instantaneous trip above 20x rating. 

Examples of heavy inductive loads:

Large motors

Electricl arc welding equipment

X-ray machines

Small particle accelerators. 

 

Fuses that allow inrush currents are also avaliable. 

 

Protective device                    Bs No           KA

semi enclosed/rewirable      BS3036        1-4

Cartridge Fuse

               Plug top type           BS1362         16.5

               Cut out type             BS88-3          33

HBC/HRC

High breaking capacity         BS88-2          Up to 80

High rating capacity

 

MCB's                                       BS60898      usually 6

RCD's                                        BS61008     Varies

RCBO's                                     BS 61009    same as MCBs

 

 

Summary: you need to know:

the 3 charactistics of overcurrent devices

Standard ratings of mcb's

 

Efects of current

Any current will produce a magnetic field

more current produces a stronger field

constant DC current produces a constant field. 

AC current produces a constantly changing alternating field

Sometimes this is very useful: motors, transformers, solenoids, relays etc. 

Sometimes it is a nuisance: stray inductance, radio interference etc. 

 

Semi enclosed fuse, BS 3036

These fuses are an older style of fuse, but there are many instsllations still using them.

 

If the fuse blows the element (wire) is replaced by the consumer!

the fuses are colour coded

White 5a

blue 15a

yellow 20a

red 30a

green 45a

 

Cartridge fuse BS1362 plug top

Max rating 13a

Also used on FCU's for fixed loads. 

 

Cartride fuse BS88-3 Usually rated at 100a for domestic supplies but can be less, 80a, 60a or sometimes 40a in very old properties.

 

BBC or HRC fuses to bs88-2

HBC = high breaking capacity

HRC = high rupture capacity

 

They are very solidly built to withstand high fault currents and the explosion of the fuse element that results. Hence breaking capacities as high as 80KA. 

 

Fuses and faults

The principle of operation for all types of fuse is: thermal (heat) 

When a normal amount of current flows.

 

IF the current increases and exceeds the rating, the fuse element melts and breaks the circuit. 

 

Arcing

If current is flowing through a circuit and a break occurs, an arc can form just as the break is starting to open. 

The arc can then be stretched out as the gap widens

Arcing can produce heat damage to switches, isolators and protective devices. 

 

Also it means current can still flow through devices that 

 

MCB's miniture circuit breaker to BS 60898 

 

Identify the various parts of the MCB 

 

Residual current device

Leftover current  device 

 

 

Discriminations between ciruits

This is achieved by having seperate overcurrent protection, each circuit has its own fuse/mcb

 

Eath fault protection also needs discrimination. This is often achieved by having circuits grouped together and protected in groups by more than one rcd. 

Having progressively lower rated cpds as we go from the supply towards the load, means that the lowest rated device upstream from the fault will operate, thereby making the circuit safe while all other devices and all other circuits are unaffected. 

 

bottom of page